Skip to main content
Loading…
This section is included in your selections.

The International Mechanical Code (IMC) Chapters 1 through 15 and Appendix A (2021 Edition) are adopted by reference to regulate all occupancies and buildings with the following revisions:

Delete all the references to the International Energy Conservation Code.

108.4 Violation Penalties. Delete the entire section. Refer to KMC Chapter 4.40.

109 Means of Appeal. Delete the entire section. Refer to KMC Chapter 4.40.

201.3 Terms Defined in Other Codes. Amend by deleting the reference to “ICC Electrical Code” and replacing it with “Electrical Code as adopted by KMC.”

Amend by deleting the reference to “International Plumbing Code” and replacing it with “Plumbing Code as adopted by KMC.”

Amend by deleting the reference to “International Fuel Gas Code” and replacing it with “Uniform Plumbing Code as adopted by KMC.”

301.2 Energy Utilization. Amend by deleting the phrase “in accordance with the International Energy Conservation Code.”

301.6 Fuel Gas Appliances and Equipment. Amend by deleting the reference to “International Fuel Gas Code” and replacing it with “Uniform Plumbing Code as adopted by KMC.”

303.3 Prohibited Locations. Amend by deleting the phrase “of the International Energy Conservation Code” from the second sentence of Exception 3.

304.9 Clearances to Combustible Construction. Amend to read:

Heat-producing equipment and appliances must be installed to maintain the required clearances to combustible construction as specified in the listing and manufacturer’s instructions. These clearances may be reduced only in accordance with Section 308 of the I.M.C. Certain unlisted, heat-producing equipment shall be allowed if equipment is installed in a manner so as to maintain the clearances to combustible construction specified in Table 304.8 of this Code. Clearances to combustibles must include such considerations as door swing, drawer pull, overhead projections or shelving and window swing, shutters, coverings, and drapes. Devices such as doorstops or limits, closers, drapery ties, or guards, may not be used to provide the required clearances.

Amend to add Table 304.9 to read:

Table 304.9. STANDARD INSTALLATION CLEARANCES IN INCHES FOR CERTAIN UNLISTED HEAT-PRODUCING APPLIANCES

Appliances

Fuel

Above Top of Casing or Appliance

From Top and Sides of Warm-Air Bonnet or Plenum

From Front1

From Back6

From Sides6

Furnaces—Floor

For mounting on combustible floors.

Solid

182

182

48

18

18

Automatic Oil or Comb. Gas-Oil

36

12

12

12

Room Heaters3

Circulating type.

Oil or Solid

36

24

12

12

Radiant or other type.

Oil or Solid

36

36

36

36

Fireplace Stove

Solid

484

54

484

484

Incinerators

Domestic types

365

48

36

36

Commercial—Type

Low Heat Appliances

Unit Heaters

Floor-mounted any size.

All fuels

18

48

18

18

Other low-heat industrial appliances.

Floor-mounted or suspended.

All fuels

18

18

48

18

18

Commercial Industrial—Type

Medium Heat Appliances

Incinerators

All sizes.

48

96

36

36

Footnotes:

1The minimum dimension shall be that necessary for servicing the appliance, including access for cleaning and normal care, tube removal, etc.

2The dimension may be 6 inches (152 mm) for an automatically stoker-fired forced-warm-air furnace equipped with 250 degree Fahrenheit limit control and with barometric draft control operated by draft intensity and permanently set to limit draft to a maximum intensity of 0.13-inch water gauge (32Pa).

3Approved appliances must be installed on non-combustible floors and may be installed on protected combustible floors. Heating appliances approved for installation on protected combustible flooring shall be so constructed that flame and hot gases do not come in contact with the appliance base. Protection for combustible floors shall consist of four-inch (102 mm) hollow masonry covered with sheet metal at least 0.021 inch (0.5 mm) thick (No. 24 manufacturer’s standard gauge). Masonry shall be permanently fastened in place in an approved manner with the ends unsealed and joints matched so as to provide free circulation of air through the masonry. Floor protection shall extend 12 inches (305 mm) at the sides and rear of the appliance, except that at least 18 inches (457 mm) shall be required on the appliance-opening side or sides measured horizontally from the edges of the opening.

4The 48-inch (1,219 mm) clearance may be reduced to 36 inches (914 mm) when protection equivalent to that provided by Items 1 through 6 of Table 304.8.1 is applied to the combustible construction.

5Clearance above the charging door must be at least 48 inches (1219 mm).

6If the appliance is encased in brick the 18-inch (457 mm) clearance above and at sides and rear may be reduced to 12 inches (305 mm).

312.1 Load Calculations. Amend the third sentence by deleting the phrase “using the design parameters specified in Chapter 3 of the International Energy Conservation Code.”

514.1 General. Amend by deleting the second sentence and replacing it with a new second sentence to read:

Energy recovery ventilation systems must be installed according to the manufacturer’s instructions and specifications.

804.1 Direct Vent Termination. Amend by adding a second sentence to read:

Combustion vents for Direct Vent Chambers are at least 3 feet high or provide snowdrift prevention and screen covers to prevent wildlife nesting or any other obstructions.

907.1 General. Amend by adding a second sentence to read:

Commercial standard UL 2790 may be accepted as an alternative to UL 791 and residential standard UL 508 and UL 698 may not be acceptable as an alternative to UL 791.

908.5 Water Supply. Amend by deleting the reference “International Plumbing Code” and replacing it with “Uniform Plumbing Code as adopted by KMC.”

931 Unvented Room Heaters. Amend by adding a new Section 931, Unvented Room Heaters, to read:

931.1 General

Unvented room heaters shall be tested in accordance with American National Standards Institute (ANSI) Z 21.11.2 and may be installed in accordance with the conditions of the listing and the manufacturer’s installation instructions.

931.2 Prohibited Use

One or more unvented room heaters may not be used as the sole source of comfort heating in a dwelling unit.

931.3 Input Rating

Unvented room heaters may not have an input rating in excess of 40,000 Btu/h (11.7 kW).

931.4 Prohibited Locations

Unvented room heaters may not be installed within A, E or I Occupancies. Such appliances may not be located in or obtain combustion air from any of the following rooms or spaces:

1. Sleeping rooms.

2. Bathrooms.

3. Toilet rooms.

4. Storage closets.

5. Surgical rooms.

Exceptions:

1. A single wall-mounted unvented room heater equipped with an oxygen depletion safety shutoff system and installed in a bathroom provided the input rating does not exceed 6,000 Btu per hour (1.76 kW) and the bathroom is not a confined space.

2. A single wall-mounted unvented room heater equipped with an oxygen depletion safety shutoff system and installed in a bedroom provided that the input rating does not exceed 10,000 Btu per hour (2.93 kW) and the bedroom is not a confined space.

931.5 Room or Space Volume

The aggregate input rating of all unvented appliances installed in a room or space may not exceed 20 Btu/h per cubic foot of volume of such room or space. Where the room or space in which the equipment is installed is directly connected to another room or space by a doorway, archway or other opening of comparable size that cannot be closed, the volume of such adjacent room or space may be permitted to be included in the calculations.

931.6 Oxygen-Depletion Safety System

Unvented room heaters will be equipped with an oxygen-depletion-sensitive safety shutoff system. The system shall shut off the gas supply to the main and pilot burners when the oxygen in the surrounding atmosphere is depleted to the percent concentration specified by the manufacturer, but not lower than 18 percent. The system will not incorporate field adjustment means capable of changing the set point at which the system acts to shut off the gas supply to room heater.

931.7 Unvented Log Heaters

An unvented log heater may not be installed in a factory-built fireplace unless the fireplace system has been specifically tested, listed and labeled for such use in accordance with Underwriters Laboratories (UL) 127.

Chapter 10 Boilers, Water Heaters, and Pressure Vessels

Amend by deleting references to “International Plumbing Code” and replacing the references with “Uniform Plumbing Code as adopted by KMC” wherever the references occur in this Chapter 10.

1001.1 Scope. Amend to read:

This chapter governs the installation, alteration and repair of boilers, water heaters, and pressure vessels not subject to the provisions of the State Department of Labor under AS 18.60.180 through 18.60.395 .

1101.4 Water Connection. Amend by deleting the reference to “International Plumbing Code” and replacing it with “Uniform Plumbing Code as adopted by KMC.”

Chapter 14 Solar Systems. Amend by deleting all references to International Plumbing Code and replacing with “Uniform Plumbing Code as adopted by KMC.”

(Ords. 2001-2003, 2089-2005, 2277-2008, 2663-2012, 3334-2023)